Welcome to Digant Technologies, your partner for Telecom Automation & Monitoring Solutions!
Digant’s Integrated Telecom Site Monitoring Solution provides the telecom tower company a consistent view of various alarms, accurate measurement of AC and DC energy consumption, diesel pilferage related alerts and diesel fuel level in real time. With the unique way of determining the fuel consumption and actual DG run hour, we are able to detect fuel pilferage accurately.
Telecom Integrated Site Monitoring Solution consists of the following components.
Integrated site controller is a versatile, reliable and ergonomically designed industrial grade product from Digant Technologies. This product reads status and fault alarm data, measures AC energy consumption and tenant wise DC energy consumption, communicates with DG controller unit at any cell tower and sends the data through GSM / GPRS medium to a central server. The system sends configurable SMS alerts to the field staff on occurrences of various events based alarms.
Operating Voltage | 19VDC to 72VDC |
Optically Isolated Alarm Input | 16 channel |
Digital Output | 4 channel |
Temperature Sensor | Built-in |
Memory Size | 2GB |
AC Energy Measurement | EB and DG |
DC Energy Measurement | 3 Channel |
Battery Bank Energy Measurement | Single channel |
Battery Backup | 4 Hours |
Wireless Interface | ISM band UHF
Frequency: 867MHz Receiver Sensitivity: -123dBm Transmit Power: +16dBm |
Communication Interface | GSM / GPRS |
GSM Band | 900 / 1800 / 850 / 1900 MHz |
Antenna | Wired antenna |
SIM Interface | Dual SIM with push and locking type |
RS485 Interface | 2x MODBUS RS485 |
Operating Temperature | - 20 °C to 60 °C |
Humidity | 95% non-condensing RH |
Housing | Metallic cabinet with security screws |
Mounting Type | Indoor / Outdoor |
DG controller unit monitors various parameters such as DG battery voltage, alarms, DG run hour and fuel level then communicates these readings to the integrated site controller. The integrated site controller sends the data to the application server at centralized location.
Power | 48VDC / DG battery |
Battery Backup | Li-ION battery, with built in Charger, minimum 4 hours backup |
Alarm Sense Inputs | 8 optically isolated inputs |
Control outputs | 2 Dry contact outputs |
Wireless Interface | ISM band UHF |
Frequency | 867MHz |
Receiver Sensitivity | -123dBm |
Transmit Power | +16dBm |
Antenna | wired antenna |
Fuel measurement accuracy | + / - 1% |
Configuration of the DG controller | Over the Air configuration from Admin dashboard via integrated site controller |
Fuel level Sensor | Fuel level sensor |
DG battery monitor | Monitors health of the DG battery |
Operating Temperature | -20 deg C to +60 deg C |
Operating Humidity | 95% non-Condensing RH |
Mounting options | Wall mount |